KORABASE

Heat exchangers

The heat exchangers KORABASE are the heart of convectors. However, its application is much wider. Imagine that you would like your heating elements to completely blend with the interior. Build your exchangers into materials, the entire interior of which is compactly created, and into places where you want to have them. A real design solution that will fulfi l even the most exacting notions of preserving the interior design.

Al/Cu heat exchanger with low water content KORABASE

It is suitable for individual installation, especially in places where compactness of interior is required in terms of materials used. If certain conditions are adhered to, the KORABASE heat exchangers can be covered with almost any material to integrate them unobstrusively into the space. The exchanger is made of copper pipes and aluminium lamellas.

Natural convection Natural convection
Heating Heating
Environmentally friendly Environmentally friendly
Minimal consumption of energy Minimal consumption of energy
Higher performance Higher performance

Technical Data

Width (mm)60, 120, 180
Height50, 110
Length (mm)800 - 3000 (at 200 mm steps)
Max. working pressure (bar)12
Max. working temperature (°C)110 °C
Connecting threadinner G 1/2“
Heat output (W)by the exchanger covering height, see the output and correction factors tables for a variant case height

Version of convectors KORABASE

EconomicEconomicexchanger with no surface finishes
ExclusiveExclusiveblack coat

Heat output [W]

Heat output calculated to ∆T= 50; (t1/t2/ti = for 75/65/20 °C)

∆T = 50 °C Length
Type 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
Typ 10 269 344 419 494 568 643 718 793 868 942 1017 1092
Typ 20 542 697 851 1006 1161 1316 1471 1625 1780 1935 2090 2245
Typ 22 636 824 1011 1198 1385 1572 1760 1947 2134 2321 2508 2696
Typ 30 685 890 1095 1299 1504 1708 1913 2118 2322 2527 2731 2936
Typ 32 948 1227 1506 1784 2063 2342 2621 2900 3178 3457 3736 4015

Temperature exponent m = 1,3

Correction factor for a different case height H

H (m)0,2000,2500,3000,3500,4000,4500,5000,5500,600
kh1,0001,0511,1361,2071,2681,3221,3711,4161,457
The case height H (m) is taken from the bottom edge of the heat exchanger lamellas. Example: conversion of the heat output of the OR-J3/-180 exchanger to the output in a case 0,45 m high. Q = 1708 x 1,416 = 2419 W

Correction factor of the cover grid´s flow surface

% of flow surface> 7560504030
correction factor1,000,950,900,850,60
The flow surface means the flow surface of the heat exchanger (widthxlength of the radiator) minus the area of the breathing grid (all dimensions given in %). The heat output of the particular convector is multiplied by this correction factor. Measurements of the performances of the Licon products include the breathing grid, therefore it is not necesery to further recalculate them.

Cross section